GMI D5011D Intrinsically Safe Isolator SIL3 2-Wire HART® Transmitter Power Supply

GET A QUOTE – For business orders requiring a written quote or for volume pricing please request a quote.

The Repeater Power Supply D5011 module is a high integrity analog input interface suitable for applications requiring SIL 3 level in safety related systems for high-risk industries. It provides a fully floating dc supply for energizing conventional 2 wires 4-20 mA transmitters located in Hazardous Areas and repeats the current in floating circuit to drive a Safe Area load. The circuit allows bi-directional communication signals, for HART® devices.

 

We are an authorized GMI distributor shipping to locations in North America.

$384.00

Connect with Hazardous Area Expert

Questions
or Volume Pricing?

Connect with Hazardous Area Expert:
281-978-2040 | Chat with Us
Get Quote

Description

  • SIL 3 / SC 3
  • Input from Zone 0/Div. 1
  • Installation in Zone 2/Div. 2
  • 4-20 mA Passive Input, Source Output
  • HART® compatible
  • Input and Output short circuit proof
  • High Accuracy
  • Three port isolation, Input/Output/Supply
  • High Density, two channels per unit

Technical Data

 

Supply

Voltage 24 Vdc nom (18 to 30 Vdc), reverse polarity protected
Current Consumption 90 mA @ 24 Vdc with 20 mA out, typical.
Power Dissipation 1.35 W @ 24 Vdc with 20 mA out, typical.

Input

Type 4 to 20 mA (2 wires Tx current limited ≈ 25 mA), reading range 0 to 24 mA.
Transmitter line voltage 15.0 V typical, 14.5 V minimum, @ 20 mA.

Output

Type 4 to 20 mA, on max. 550 Ω load in source mode (typical 12 V compliance).
Response time 5 ms (0 to 100 % step change).

Performance

Ref. Conditions 24 V supply, 250 Ω load, 23 ± 1 °C ambient temperature.
Calibration accuracy ≤ ± 0.1 % FSR.
Linearity accuracy ≤ ± 0.05 % FSR.
Temp. influence ≤ ± 0.01 % FSR on zero/span for a 1 °C change.

Isolation

Test Voltage I.S. In/Out 2.5 kV; I.S. In/Supply 2.5 kV; I.S. In/I.S. In 500 V; Out/Supply 500 V; Out/Out 500 V.

Environmental conditions

Operating temperature temperature limits –40 to +70 °C.
Storage temperature temperature limits –45 to +80 °C.

Safety description

Equipment Associated apparatus and non-sparking electrical equipment.
Safety parameters Uo = 25.9 V, Io = 92 mA, Po = 594 mW at terminals 7-8, 9-10. Um = 250 Vrms or Vdc, -40 °C ≤ Ta ≤ 70 °C.

Mounting

Type DIN-Rail 35 mm, with or without Power Bus or on custom Term. Board.
Weight about 140 g
Connection by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm² (13 AWG).
Dimensions Width 12.5 mm, Depth 123 mm, Height 120 mm.

Resources

Datasheet
Instruction Manual
Safety Manual
ATEX Certificate
IECEx Certificate
UL Certificate
FM Certificate
EU Declaration of Conformity

Approvals

 

ATEX: II 3(1)G Ex ec [ia Ga] IIC T4 Gc, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I
IECEx / INMETRO: Ex ec [ia Ga] IIC T4 Gc, [Ex ia Da] IIIC, [Ex ia Ma] I
UL: NI / I / 2 / ABCD / T4, AIS / I, II, III / 1 / ABCDEFG, AEx nA [ia Ga] IIC T4 Gc
C-UL: NI / I / 2 / ABCD / T4, AIS / I, II, III / 1 / ABCDEFG, Ex nA [ia Ga] IIC T4 Gc
FM: NI-AIS / I / 2 / ABCD / T4, AIS / I,II,III / 1 / ABCDEFG, I / 2 / AEx nA [ia] / IIC / T4
FMC: NI-AIS / I / 2 / ABCD / T4, AIS / I,II,III / 1 / ABCDEFG, I / 2 / Ex nA [ia] / IIC / T4
EAC-EX: 2Ex nA [ia Ga] IIC T4 Gc X, [Ex ia Da] IIIC X, [Ex ia Ma] I X
CCC: Ex ec [ia Ga] IIC T4 Gc; [Ex ia Ga] IIC; [Ex ia Da] IIIC
UKR TR n. 898: 2ExnAiaIICT4 X, ExiaI X
associated apparatus and non-sparking electrical equipment.
Uo/Voc = 25.9 V, Io/Isc = 92 mA, Po/Po = 594 mW at terminals 7-8, 9-10.
Um = 250 Vrms, -40 °C ≤ Ta ≤ 70 °C.

HAZARDOUS AREA INSTRUMENTS
BACKED WITH INDUSTRY LEADING SERVICE AND SUPPORT

Download Product and Service Catalogs

Fill out your contact details and we will forward you to download our product brochures. 

HAZARDOUS AREA INSTRUMENTS