Exloc Instruments Logo
Search
Close this search box.

Flashing Alarm Beacons

INTRINSICALLY SAFE FLASHING ALARM BEACONS

Provide Alarm Notification in Hazardous Locations & Extreme Environments

IS-MB1 I.S. LED FLASHING BEACON

  • Intrinsically safe
  • FM, ATEX & IECEx certification
  • Takes 16-28 VDC from suitable safety barrier
  • Six high-intensity LEDs
  • Double flash at once or twice per second
  • IP65 ABS flame retardant housing
  • End-of-line (EOL) resistor certification
  • Economical solution for industrial fire & gas detection systems
IS-MB1 SPECIFICATIONS
Certification Factory Mutual: Cl I, Div 1, Grp A-D; Class I, Zone 0, AEx ia IIC T4 ATEX & IECEx: II 1G EEx ia IIC T4 (-40°C<=Ta<=+60°C)
Operating Voltage 16-28VDC via Zener or galvanically isolated safety barrier
Current Draw 25mA typical when powered from 24VDC via a safety barrier; beacon has internal current limiting and reverse current protection
Light Source Six high intensity LEDs with prismatic lens to optimize LED visibility
Light Output Double flash in two configurable modes: 1Hz / 2Hz
Lens Colors Red, orange/amber, green, blue, clear
Dimensions 3.35″ h x 3.74″ dia* / 85 h x 95 dia* mm. *Inc. lens fastener protrusion
Operating Temperature -40 to +140°F / -40 to +60°C
Environmental Ingress protection: IP65Housing material: ABS flame retardant; Lens: polycarbonate.Relative humidity: 90% max. @ 120°F / 50°C
Cable Entry 2x M20 knockouts
Other End-of-line (EOL) resistor certified for fire & gas alarm systems

[vc_accordion][vc_accordion_tab title=”IS-MB1 Beacon, Barrier Recommendations” open=”0″]

Option 1 – single beacon installation:

The IS-MB1 Beacon requires a single intrinsic safety barrier with safety/entity parameters not exceeding the following values:
Uo/Voc=28V, Io/Isc=660mA, Po/Po=1.2W.
Suitable barrier: GMI D1048S / D1049S / D5048S / D5049S using output “A” terminals in each case.

Option 2 – multiple beacons, use of multi-channel barrier for economy:

Suitable barrier: GMI D1042Q (quad channel) with each output separately powering an individual IS-MB1 beacon.

Note that while each beacon has it’s own dedicated barrier channel, a complete failure of the barrier module will affect all alarm notifications associated with it.

IS-MC1 I.S. COMBINATION LED FLASHING BEACON & ALARM SOUNDER

  • Intrinsically safe
  • FM, ATEX & IECEx certification
  • Takes 16-28 VDC from suitable safety barrier
  • Six high-intensity
  • LEDs
  • Prismatic lens in choice of five colors
  • Double flash at once or twice per second
  • Loud 100 dB(A) audible output
  • Choice of 49 alarm tone combinations, 3 stages
  • IP65 ABS flame retardant housing
  • End-of-line (EOL) resistor certification
  • Economical solution provides visible and audible alarm in one compact unit
  • Perfect for industrial fire & gas alarm systems
IS-MB1 SPECIFICATIONS
Certification Factory Mutual: Cl I, Div 1, Grp A-D; Class I, Zone 0, AEx ia IIC T4 ATEX & IECEx: II 1G EEx ia IIC T4 (-40°C<=Ta<=+60°C)
Operating Voltage 16-28VDC via Zener or galvanically isolated safety barrier
Current Draw 25mA each typical for beacon and sounder powered separately from 24VDC via safety barriers, 30mA total typical when beacon and sounder are powered from a common barrier; unit has internal current limiting and reverse current protection
Light Source Six high intensity LEDs with prismatic lens to optimize LED visibility
Light Output Double flash in two configurable modes: 1Hz / 2Hz
Lens Colors Red, orange/amber, green, blue, clear
Alarm Sound Output 100 dB(A) @ 1 m; effective range up to 130′ / 40 m @ 1kHZ Sample Alarm Tones
Alarm Sound Modes 49 configurable tone combinations, 3 stages (PFEER/UKOOA compliant)
Dimensions 4.60″ h x 3.74″ dia* / 116 h x 95 dia* mm. *Inc. lens fastener protrusion
Operating Temperature -40 to +140°F / -40 to +60°C
Environmental Ingress protection: IP65Housing material: ABS flame retardant; Lens: polycarbonate.Relative humidity: 90% max. @ 120°F / 50°C
Cable Entry 2x M20 knockouts
Other End-of-line (EOL) resistor certified for fire & gas alarm systems

IS-MC1 COMBINATION BEACON & SOUNDER

Barrier Recommendations

Option 1 – mutual two-wire power connection:


The IS-MC1 Combination Beacon & Sounder may be powered from a single intrinsic safety barrier providing 16VDC @ 35mA and with safety/entity parameters not exceeding the following values:
Uo/Voc=28V, Io/Isc=93mA, Po/Po=660mW.
Suitable barriers: P&F KFDO-SD2-Ex1.1045; MTL5025
Note that failure of the single barrier will negate both alarm notification modes.

Option 2 – high integrity four-wire connection, beacon and sounder powered separately:

The beacon requires a single intrinsic safety barrier with safety/entity parameters not exceeding the following values:
Uo/Voc=28V, Io/Isc=660mA, Po/Po=1.2W.
Suitable barrier: GMI D1048S / D1049S / D5048S / D5049S using output “A” terminals in each case.

The sounder requires a single intrinsic safety barrier with safety/entity parameters not exceeding the following values:
Uo/Voc=28V, Io/Isc=93mA, Po/Po=660mW.
Suitable barrier: GMI D1048S / D1049S / D5048S / D5049S using output “C” terminals in each case.

Note that the failure of one barrier will leave the other alarm notification mode working.

Option 3 – multiple IS-MC1 beacon & sounder combos, use of multi-channel barrier for economy:

Suitable barrier: GMI D1042Q (quad channel) with each output separately powering either a beacon or a sounder. Under no circumstances may two barrier channel outputs be connected in parallel to power one beacon-sounder combination.

Note that while each beacon and sounder has it’s own dedicated barrier channel, a complete failure of the barrier module will negate all alarm notifications associated with it.

Sounder Stage 2 Control (only): D1044S (single channel)

Sounder Stage 2 & 3 Control: D1044D (dual channel, one channel used per control line)

IS-MC1 I.S. COMBINATION LED FLASHING BEACON & ALARM SOUNDER

  • Intrinsically safe
  • FM, ATEX & IECEx certification
  • Takes 16-28 VDC from suitable safety barrier
  • Six high-intensity LEDs
  • Prismatic lens in choice of five colors
  • Double flash at once or twice per second
  • Loud 100 dB(A) audible output
  • Choice of 49 alarm tone combinations, 3 stages
  • IP65 ABS flame retardant housing
  • End-of-line (EOL) resistor certification
  • Economical solution provides visible and audible alarm in one compact unit
  • Perfect for industrial fire & gas alarm systems
IS-MB1 SPECIFICATIONS
Certification Factory Mutual: Cl I, Div 1, Grp A-D; Class I, Zone 0, AEx ia IIC T4 ATEX & IECEx: II 1G EEx ia IIC T4 (-40°C<=Ta<=+60°C)
Operating Voltage 16-28VDC via Zener or galvanically isolated safety barrier
Current Draw 25mA each typical for beacon and sounder powered separately from 24VDC via safety barriers, 30mA total typical when beacon and sounder are powered from a common barrier; unit has internal current limiting and reverse current protection
Light Source Six high intensity LEDs with prismatic lens to optimize LED visibility
Light Output Double flash in two configurable modes: 1Hz / 2Hz
Lens Colors Red, orange/amber, green, blue, clear
Alarm Sound Output 100 dB(A) @ 1 m; effective range up to 130′ / 40 m @ 1kHZ Sample Alarm Tones
Alarm Sound Modes 49 configurable tone combinations, 3 stages (PFEER/UKOOA compliant)
Dimensions 4.60″ h x 3.74″ dia* / 116 h x 95 dia* mm. *Inc. lens fastener protrusion
Operating Temperature -40 to +140°F / -40 to +60°C
Environmental Ingress protection: IP65Housing material: ABS flame retardant; Lens: polycarbonate.Relative humidity: 90% max. @ 120°F / 50°C
Cable Entry 2x M20 knockouts
Other End-of-line (EOL) resistor certified for fire & gas alarm systems

IS-MC1 COMBINATION BEACON & SOUNDER

Barrier Recommendations

Option 1 – mutual two-wire power connection:

The IS-MC1 Combination Beacon & Sounder may be powered from a single intrinsic safety barrier providing 16VDC @ 35mA and with safety/entity parameters not exceeding the following values:
Uo/Voc=28V, Io/Isc=93mA, Po/Po=660mW.
Suitable barriers: P&F KFDO-SD2-Ex1.1045; MTL5025
Note that failure of the single barrier will negate both alarm notification modes.

Option 2 – high integrity four-wire connection, beacon and sounder powered separately:

The beacon requires a single intrinsic safety barrier with safety/entity parameters not exceeding the following values:
Uo/Voc=28V, Io/Isc=660mA, Po/Po=1.2W.
Suitable barrier: GMI D1048S / D1049S / D5048S / D5049S using output “A” terminals in each case.

The sounder requires a single intrinsic safety barrier with safety/entity parameters not exceeding the following values:
Uo/Voc=28V, Io/Isc=93mA, Po/Po=660mW.
Suitable barrier: GMI D1048S / D1049S / D5048S / D5049S using output “C” terminals in each case.

Note that the failure of one barrier will leave the other alarm notification mode working.

Option 3 – multiple IS-MC1 beacon & sounder combos, use of multi-channel barrier for economy:

Suitable barrier: GMI D1042Q (quad channel) with each output separately powering either a beacon or a sounder. Under no circumstances may two barrier channel outputs be connected in parallel to power one beacon-sounder combination.

Note that while each beacon and sounder has it’s own dedicated barrier channel, a complete failure of the barrier module will negate all alarm notifications associated with it.

Sounder Stage 2 Control (only): D1044S (single channel)

Sounder Stage 2 & 3 Control: D1044D (dual channel, one channel used per control line)

BA386 I.S. LED FLASHING BEACON

  • Intrinsically safe
  • FM and ATEX certification
  • Choice of five colors
  • Two double flashes per second
  • IP56 environmental rating
  • Compatible with a wide range of barriers
  • Can power BR385 sounder with same safety barrier


The BA386 provides a bright flashing warning signal in a plant or processing area where ambient noise levels may drown out an audible alarm. It is significantly less expensive than traditional Xenon devices, yet has a similar light output and flashes more rapidly – making it more immediately noticable. Available in five colors to enable multi-stage alarm level protocols. Factory Mutual and ATEX intrinsic safety certification enable it to be used in virtually any classified hazardous location.

Can be used in conjunction with a BR385 alarm sounder using a single galvanically isolated barrier. The BA386 beacon includes terminals to power the sounder, and for an external push button to silence the sounder. The silence time is adjustable from 1 to 30 minutes. We can even supply a kit to combine the two units.

BA386 BEACON & BR385 SOUNDER COMBINATION,
BARRIER RECOMMENDATIONS
Option 1 – mutual two-wire connection:

The BA386 Beacon & BR385 Sounder Combination may be powered from a single intrinsic safety barrier providing 16VDC @ 35mA and with safety/entity parameters not exceeding the following values:
Uo/Voc=28V, Io/Isc=93mA, Po/Po=660mW.
Suitable barriers: P&F KFDO-SD2-Ex1.1045; MTL5025

Note that failure of the single barrier will negate both alarm notification modes.

Option 2 – high integrity four-wire connection, beacon and sounder powered separately:

The BA386 Beacon requires a single intrinsic safety barrier with safety/entity parameters not exceeding the following values:
Uo/Voc=28V, Io/Isc=110mA, Po/Po=800mW.
Suitable barrier: GMI D1048S / D1049S / D5048S / D5049S using output “B” terminals in each case.

The BR385 Sounder requires a single intrinsic safety barrier with safety/entity parameters not exceeding the following values:
Uo/Voc=28V, Io/Isc=93mA, Po/Po=660mW.
Suitable barrier: GMI D1048S / D1049S / D5048S / D5049S using output “C” terminals in each case.

Note that the failure of one barrier will leave the other alarm notification mode working.

Option 3 – multiple beacon & sounder combos, use of multi-channel barrier for economy:

Suitable barrier: GMI D1042Q (quad channel) with each output separately powering either a beacon or a sounder. Under no circumstances may two barrier channel outputs be connected in parallel to power one beacon-sounder combination.

Note that while each beacon and sounder has it’s own dedicated barrier channel, a complete failure of the barrier module will negate all alarm notifications associated with it.

BA386 BEACON & BR385 SOUNDER COMBINATION,
BARRIER RECOMMENDATIONS
Option 1 – mutual two-wire connection:

The BA386 Beacon & BR385 Sounder Combination may be powered from a single intrinsic safety barrier providing 16VDC @ 35mA and with safety/entity parameters not exceeding the following values:
Uo/Voc=28V, Io/Isc=93mA, Po/Po=660mW.
Suitable barriers: P&F KFDO-SD2-Ex1.1045; MTL5025

Note that failure of the single barrier will negate both alarm notification modes.

Option 2 – high integrity four-wire connection, beacon and sounder powered separately:

The BA386 Beacon requires a single intrinsic safety barrier with safety/entity parameters not exceeding the following values:
Uo/Voc=28V, Io/Isc=110mA, Po/Po=800mW.
Suitable barrier: GMI D1048S / D1049S / D5048S / D5049S using output “B” terminals in each case.

The BR385 Sounder requires a single intrinsic safety barrier with safety/entity parameters not exceeding the following values:
Uo/Voc=28V, Io/Isc=93mA, Po/Po=660mW.
Suitable barrier: GMI D1048S / D1049S / D5048S / D5049S using output “C” terminals in each case.

Note that the failure of one barrier will leave the other alarm notification mode working.

Option 3 – multiple beacon & sounder combos, use of multi-channel barrier for economy:

Suitable barrier: GMI D1042Q (quad channel) with each output separately powering either a beacon or a sounder. Under no circumstances may two barrier channel outputs be connected in parallel to power one beacon-sounder combination.

Note that while each beacon and sounder has it’s own dedicated barrier channel, a complete failure of the barrier module will negate all alarm notifications associated with it.

DA135 I.S. LED FLASHING BEACONS

  • Intrinsically safe
  • ATEX II 1 G EEx ia IIC T6
  • Choice of five colors
  • Single, dual, or triple flash modes
  • Dual color option
  • IP65 environmental rating
  • May be combined with sounder and pushbutton
  • Isolated control connections
  • Compatible with a wide range of barriers
  • Pipe or wall mounting
Exloc Instruments

DA135 beacons offer multiple alarm modes to provide visual warnings in a variety of situations. A choice of five bright colors – including blue and white – plus single, dual and triple flash cycles. There’s even a dual color option to warn operators of a relative change in status. Protective lenses appear clear until the LEDs are illuminated. Each beacon may be connected to a sounder and acknowledge/reset pushbutton to create a local alarm station. The electronics are totally encapsulated, and wiring connections are made in a separate terminal chamber. All control connections are fully isolated to simplify circuit design.

More DA135

Information

Data Sheet

User Manual

ATEX Certificate

Get Quotation

DA135 BEACON, BARRIER RECOMMENDATIONS

Option 1 – single beacon installation:

The DA135 Beacon requires a single intrinsic safety barrier with safety/entity parameters not exceeding the following values:
Uo/Voc=28V, Io/Isc=110mA, Po/Po=800mW.
Suitable barrier: GMI D1048S / D1049S / D5048S / D5049S using output “B” terminals in each case.

Option 2 – multiple beacons, use of multi-channel barrier for economy:

Suitable barrier: GMI D1042Q (quad channel) with each output separately powering an individual BA386 beacon.

Note that while each beacon has it’s own dedicated barrier channel, a complete failure of the barrier module will affect all alarm notifications associated with it.

DA135 BEACON & BR385 SOUNDER COMBINATION

Barrier Recommendations

Option 1 – mutual two-wire connection:

The DA135 Beacon & BR385 Sounder Combination may be powered from a single intrinsic safety barrier with safety/entity parameters not exceeding the following values:
Uo/Voc=28V, Io/Isc=93mA, Po/Po=660mW.
Suitable barriers: P&F KFDO-SD2-Ex1.1045; MTL5025

Note that failure of the single barrier will negate both alarm notification modes.

Option 2 – high integrity four-wire connection, beacon and sounder powered separately:

The DA135 Beacon requires a single intrinsic safety barrier with safety/entity parameters not exceeding the following values:
Uo/Voc=28V, Io/Isc=110mA, Po/Po=800mW.
Suitable barrier: GMI D1048S / D1049S / D5048S / D5049S using output “B” terminals in each case.

The BR385 Sounder requires a single intrinsic safety barrier with safety/entity parameters not exceeding the following values:
Uo/Voc=28V, Io/Isc=93mA, Po/Po=660mW.
Suitable barrier: GMI D1048S / D1049S / D5048S / D5049S using output “C” terminals in each case.

Note that the failure of one barrier will leave the other alarm notification mode working.

Option 3 – multiple beacon & sounder combos, use of multi-channel barrier for economy:

Suitable barrier: GMI D1042Q (quad channel) with each output separately powering either a beacon or a sounder. Under no circumstances may two barrier channel outputs be connected in parallel to power one beacon-sounder combination.

Note that while each beacon and sounder has it’s own dedicated barrier channel, a complete failure of the barrier module will negate all alarm notifications associated with it.

HAZARDOUS AREA INSTRUMENTS
BACKED WITH INDUSTRY LEADING SERVICE AND SUPPORT

Download Product and Service Catalogs

Fill out your contact details and we will forward you to download our product brochures. 

HAZARDOUS AREA INSTRUMENTS
BACKED WITH INDUSTRY LEADING SERVICE AND SUPPORT